CVE-2026-101022 PUBLISHED

Grid Protection Alliance openPDC and openHistorian Server-Side Request Forgery (SSRF)

Assigner: icscert
Reserved: 05.10.2026 Published: 09.10.2026 Updated: 09.10.2026

A Modbus connection feature on openPDC accepts a caller-specified destination address and port with no restriction on which internal hosts may be targeted. An authenticated user can attempt connections to arbitrary internal network destinations, revealing which destinations are reachable. With repeated attempts, an attacker may be able to map the internal network.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N
CVSS Score: 5.3

Product Status

Vendor Grid Protection Alliance
Product openPDC
Versions Default: unaffected
  • affected from 0 to 2.9.477 (excl.)
  • affected from 0 to 2.9.482 (excl.)
  • Version 2.9.482 is unaffected
Vendor Grid Protection Alliance
Product openPDC (Docker image)
Versions Default: unaffected
  • affected from 0 to 2.9.477 (excl.)
  • affected from 0 to 2.9.482 (excl.)
Vendor Grid Protection Alliance
Product openHistorian
Versions Default: unaffected
  • affected from 0 to 2.8.580 (excl.)
  • affected from 0 to 2.8.585 (excl.)
  • Version 2.8.585 is unaffected

Workarounds

Grid Protection Alliance recommends restricting network access to modbus using a firewall, and disallowing connections to loopback and private (RFC 1918) address ranges unless explicitly required.

Credits

  • Shubham Raj (Cipher) of Causal Security reported this vulnerability to CISA. finder

References

Problem Types

  • CWE-918 CWE