CVE-2026-12562 PUBLISHED

Toptech Systems RCU II+ and Multiload II+ Missing Authentication for Critical Function

Assigner: icscert
Reserved: 17.06.2026 Published: 30.07.2026 Updated: 30.07.2026

The RCU II+ and Multiload II+ are vulnerable to an unauthenticated service that exposes a debug interface granting full root-level access to the embedded system. This vulnerability stems from a network-accessible port running a Target Communications Framework (TCF) service that does not require any authentication, allowing an attacker to directly interact with the Linux environment that powers the device. Once connected, an attacker can freely view and modify the filesystem, manipulate running processes, and control network interfaces, enabling deep alteration of system behavior.

Metrics

CVSS Vector: CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CVSS Score: 8.7

Product Status

Vendor Toptech Systems
Product RCU II+
Versions Default: unaffected
  • affected from 0 to 2025-11-24 (excl.)
Vendor Toptech Systems
Product Multiload II+
Versions Default: unaffected
  • affected from 0 to 2025-11-24 (excl.)

Solutions

Toptech Systems provides two methods for remediating affected RCU II+ and Multiload II+ units: First, move the device to a closed or segmented network without untrusted access.

Run one of the RCU II+/Multiload II+ Vulnerability Removal Tools (VRT) available at https://s3.amazonaws.com/docs.toptech.com/nonpublic/rcuiip_mliip_vrt.zip ,

https://s3.amazonaws.com/docs.toptech.com/nonpublic/rcuiip_mliip_vrt.gz.

  • This option does not require breaking Weights and Measures seals and has the least operational impact.

Install the latest firmware from https://s3.amazonaws.com/docs.toptech.com/index.html#downloads/Firmware/RCUII+_MLII+_SMPII+/ . * This method requires stopping the bay and breaking the W&M seal. Be sure to back up the current ML configuration before performing the firmware update.

For questions, contact Toptech Systems Support at security@toptech.com. Additional details are available in Toptech System's firmware vulnerability notice: https://s3.amazonaws.com/docs.toptech.com/nonpublic/2025%2012%2001%20RCU%20IIPlus%20MultiLoad%20IIPlus%20Vulnerability%20Notice.pdf .

Credits

  • Donald Green of Southwest Research Institute reported this vulnerability to CISA. finder

References

Problem Types

  • CWE-306 CWE