CVE-2026-27843 PUBLISHED

SenseLive X3050 Missing authentication for critical function

Assigner: icscert
Reserved: 14.04.2026 Published: 23.04.2026 Updated: 23.04.2026

A vulnerability exists in SenseLive X3050's web management interface that allows critical configuration parameters to be modified without sufficient authentication or server-side validation. By applying unsupported or disruptive values to recovery mechanisms and network settings, an attacker can induce a persistent lockout state. Because the device lacks a physical reset button, recovery requires specialized technical access via the console to perform a factory reset, resulting in a total denial-of-service for the gateway and its connected RS-485 downstream systems.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:H
CVSS Score: 9.2

Product Status

Vendor SenseLive
Product X3050
Versions Default: unaffected
  • Version V1.523 is affected

Solutions

SenseLive did not respond to CISA's requests to coordinate. Affected users are encouraged to reach out to SenseLive for more information. https://senselive.io/contact

Credits

  • Jithin Nambiar J reported these vulnerabilities to CISA. finder

References

Problem Types

  • CWE-306 Missing authentication for critical function CWE