CVE-2026-29797 PUBLISHED

Red Lion Controls N-Tron 700 Series Download of Code Without Integrity Check

Assigner: icscert
Reserved: 08.04.2026 Published: 09.10.2026 Updated: 09.10.2026

No authentication is required when updating firmware or bootloader, making it easy for malicious files to be pushed to the device. Additionally, anyone with the same software can scan a network for N-Tron devices and push/pull firmware without authenticating by using SNMP/TFTP.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:H/VA:N/SC:L/SI:H/SA:N
CVSS Score: 8.4

Product Status

Vendor Red Lion Controls
Product 700 Series
Versions Default: unaffected
  • affected from 0 to Firmware Versions 3.11.0 (excl.)
  • affected from 0 to Bootloader Versions 2.0.6.1 (excl.)
  • Version 3.11.1 is unaffected

Solutions

Red Lion controls recommends the following upgrades for the N-Tron 700 Series:

  • Upgrade to firmware version 3.11.1 or greater
  • Configure or disable the SNMP communities
  • Disable access to the web GUI

The upgrade procedure document can be viewed here https://www.hms-networks.com/ .

The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here https://www.hms-networks.com/cybersecurity .

Credits

  • Gabrianna (Ria) Milloway of Idaho National Laboratory reported this vulnerability to CISA. finder

References

Problem Types

  • CWE-494 CWE