CVE-2026-3611 PUBLISHED

Honeywell IQ4x BMS Controller Missing authentication for critical function

Assigner: icscert
Reserved: 05.03.2026 Published: 12.03.2026 Updated: 13.03.2026

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H
CVSS Score: 10

Product Status

Vendor Honeywell
Product IQ4E
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQ412
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQ422
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQ4NC
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQ41x
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQ3
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)
Vendor Honeywell
Product IQECO
Versions Default: unaffected
  • affected from v3.50_3.44 to 4.36 (build 4.3.7.9) (incl.)

Workarounds

Honeywell is aware of the issue, but has not released a fix. For more information, contact Honeywell directly. https://www.honeywell.com/us/en/contact.

Credits

  • Gjoko Krstic of Zero Science reported this vulnerability to Honeywell. finder

References

Problem Types

  • CWE-306 Missing authentication for critical function CWE