CVE-2026-4769 PUBLISHED

Unauthenticated Access to Internal Diagnostic Interface

Assigner: CERTVDE
Reserved: 24.03.2026 Published: 13.07.2026 Updated: 13.07.2026

Certain devices in the WAGO System I/O Field series activate an internal diagnostic capability during the initial startup sequence. This functionality is not formally documented and becomes accessible without authentication for a brief period in the early boot phase. During this window, an unauthenticated remote attacker can gain access to the internal system processes, resulting in full system compromise.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CVSS Score: 9.3

Product Status

Vendor WAGO
Product 0765-110x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.1.100 (excl.)
Vendor WAGO
Product 0765-120x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.7.100 (excl.)
Vendor WAGO
Product 0765-150x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.7.103 (excl.)
Vendor WAGO
Product 0765-2101/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.1.102 (excl.)
Vendor WAGO
Product 0765-2102/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.5.101 (excl.)
Vendor WAGO
Product 0765-410x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.1.100 (excl.)
Vendor WAGO
Product 0765-420x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.7.100 (excl.)
Vendor WAGO
Product 0765-450x/0100-0000
Versions Default: unaffected
  • affected from 1.0.0.0 to 1.2.7.103 (excl.)

References

Problem Types

  • CWE-912 Hidden Functionality CWE