CVE-2026-58115 PUBLISHED

Assigner: siemens
Reserved: 29.06.2026 Published: 11.08.2026 Updated: 11.08.2026

A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.

Metrics

CVSS Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H
CVSS Score: 10

Product Status

Vendor Siemens
Product SIMATIC IoT2050 Advanced
Versions Default: unknown
  • affected from 0 to V4.3.4.1 (excl.)

References

Problem Types

  • CWE-306: Missing Authentication for Critical Function CWE