CVE-2026-9108 PUBLISHED

Studio 5000 Logix Designer® – Multiple Vulnerabilities

Assigner: Rockwell
Reserved: 20.05.2026 Published: 14.07.2026 Updated: 14.07.2026

A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.

Metrics

CVSS Vector: CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CVSS Score: 5.4

Product Status

Vendor Rockwell Automation
Product Studio 5000 Logix Designer
Versions Default: unaffected
  • Version V36.00, 35.00,35.01, 34.00-34.03, 33.00-33.03, 32.00-32.04 and older is affected

References

Problem Types

  • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') CWE